info@aykome.com.tr

+90 312 251 22 00

NON CONTACT WATER LEVEL SENSOR

The Orakel Primary device system is a non contact water level sensor. It comprises an ORAKEL controller and an external level transducer.

An intuitive and versatile flow module is built into the Orakel. It works by converting level readings to flow measurements using standardised formulas.

This product is particularly well suited to measuring flows through weirs and flumes.

KEY FEATURES
ULTRASONIC LEVEL SENSOR
Sophisticated method of determining surface level and therefore depth

Easily fine-tuned to the site parameters

High performance echo discrimination Loop powered

ATEX Zone 1 approved

ORAKEL ANALYSER
A compact electronic control and communication system

4″ colour screen with nine-button keypad for control and data entry

Internal SD card logging

Multiple language selection IP65 splash-proof casing

Analogue outputs for data loggers and SCADA systems

2 relays as standard

OPTIONAL ACCESSORIES

Multichannel GSM data logger and webhosting

Full Detectronic Datacentre package

ATEX Zone 1 galvanic isolator and sealed enclosure

Additional water quality sensors

TECHNICAL SPECIFICATION
ORAKEL ANALYSER
POWER: 100-240VAC/0.25A or 12VDC/0.8A.

INPUTS: Up to 4 configurable sensor inputs.

OUTPUTS: Up to 4 configurable outputs.

DIMENSIONS: 309 x 230 x 103mm.

WEIGHT: 2kg.

IP RATING: IP65, Nema 4X.

ENCLOSURE MATERIAL: flame retardant ABS.

ULTRASONIC LEVEL SENSOR
LOOP POWERED: 4-20mA.

RANGE: 0.125-3m.

ACCURACY: 2mm. IP68 sealed. Ex mb ATEX certified. Programmable with HART modem.

DIMENSIONS: 77mm dia. x 134mm.

WEIGHT: 1kg.

OPERATING RANGE: -40°C to 80°C.